Technical Specification
Model |
Max Capacity (Litres) |
Overall Diameter (mm) |
Length (mm) |
Inlet Pipework (Standard Options) |
Inlet Invert Depth* (mm) |
Outlet Invert Depth* (mm) |
Overall Height (mm) |
PSTOR18E-01 | 8040 | 1912 | 3238 |
Ø110 mm Ø160 mm Ø200 mm Ø250 mm Ø315 mm |
600 | 700 | 2400 |
PSTOR18E-02 | 10010 | 1912 | 3970 | ||||
PSTOR18E-03 | 12140 | 1912 | 4750 | 1000 | 1100 | 2800 | |
PSTOR18E-04 | 15080 | 1912 | 5788 | ||||
PSTOR18E-05 | 19340 | 1912 | 7386 | 1500 | 1600 | 3300 | |
PSTOR18E-06 | 25300 | 1912 | 9435 | ||||
PSTOR18E-07 | 29550 | 1912 | 11012 | 2000 | 2100 | 3800 |
*Notes: Inlet inverts are available for all tank range options
Product Description
The new Kingspan Klargester extended PSTOR Horizontal Pump Range, is engineered for reliable performance offering complete peace of mind.
The new range offers a simplified and economic alternative providing two new options including a 1.8m and 2.8m diameter tank size, with a range of capacities from 8000 - 79000 litres.
In the event of power supply failure, this packaged pumping station swiftly initiates a process to segregate liquids and solids into distinct chambers, enabling temporary waste storage for a period of up to 24 hours. Upon power restoration, the system seamlessly resumes standard pump operations, ensuring uninterrupted functionality.
For a price guide, please select the Technical Specification tab to identify the pumping station capacity required.
Why Choose a Klargester Pump Station?
- Designed as a single piece chamber for easy installation.
- Totally sealed system.
- Suitable for shallow dig.
- Standard invert extended to 5m on 2.8m tank.
- High level alarm for complete piece of mind.
- Wider range of install options.
PSTOR Key Features and Benefits
-
Two new options available, including a 1.8m and 2.8m diamater tank size
-
Includes removable filters, a high-level alarm
-
Easy and simple on-site assembly of pump station
-
Completely sealed system
-
High-level alarm for complete peace of mind
-
Free site visit to help select the model to meet your needs - complete the site visit request form here
-
Less cranage and shallower excavation than concrete pumping stations
-
SmartServ Pro remote monitoring solution available for added peace of mind (optional extra)
-
Multiple valve chamber location and invert options
-
Single-tank installation up to 79m3 (multiple tank systems available)
-
Affordable service and maintenance plans are available
Product Details
- Product Code: KLA
- Customer Offloading: Customer Offloading
- Diameter: 1800mm
- Free Site Survey: Free Site Survey
- HIAB Available: HIAB Available
- Material: GRP
- Twin or Single: Twin
Do you require Commissioning?
Do you require Commissioning?
Low Cost Commissioning
Benefits:
- Reassurance that your system's mechanical and electrical components are in good working order
- A warranty period that only starts when your water system is commissioned, not when it leaves the factory (terms and conditions apply)
- Trouble-free operation of your system from the start
To find out more about what's included in the Commissioning of your Kingspan Klargester pump station, or to arrange Commissioning, please click here for more information
Smart Commissioning – Standard commissioning as scope of works, inc supplied and fitted (at point of commissioning) Kingspan Smartserv Pro GSM telemetry alarm for complete peace of mind. Smartserv alerts both Kingspan and designated contacts. Includes 3 years Kingspan monitoring free of charge. (T&Cs apply).
Standard Commissioning
The checks below will be carried out by a Kingspan Service Engineer and will only be checked if the unit has been installed in line with the provided installation guidelines.
- Unit is installed flat and level with safe working area around the perimeter
- All incoming and outgoing pipework has been connected
- Permanent electrical supply has been fitted to the panel (extension leads or generator supplies will not be acceptable)
- The following will then be carried out by an Authorised Service Engineer:
- Check the system is installed to manufacturer's instruction
- Fit floats in tank and set the levels
- Pull float and pump cables through the ducts using drawstring provided
- Connect pump and float cables to the control panel using appropriate glands (the panel must be within 2 m of the chamber or select “enhanced commissioning”)
- Check float cable operation and terminate (stop, start, standby, alarm)
- Check pump rotation
- Run the pumps via the float switches to ensure correct operation and discharge
- Test high level alarm and beacon (if applicable)
- Leave on Auto for future use
Please note, Kingspan Commissioning covers UK mainland and certain postcode areas only. Please speak to our Team for expert advice on Commissioning.
Service and maintenance
Your pump station should be serviced bi-annually to prevent blockages or obstructions in the inlet or outlet pipes from occurring. Any service and maintenance works need to be carried out by a properly trained professional, with appropriate experience, especially with mechanical and electrical parts. For more information on service and maintenance plans, please give our team a call on 0808 167 6376.
Delivery
Our shipping costs cover most of the UK - however, parts of England, Scottish Highlands and Islands including areas north of the Glasgow / Edinburgh border, Isle of Wight, Channel Islands, Isle of Man, Anglesey, Western Isles, Shetland Islands, Orkney Islands, Isles of Scilly, Northern Ireland and the Republic of Ireland may cost more.
Please call before ordering if the delivery postcode is listed below. There may be additional shipping costs. AB, BT, CA, CT, DD, DG, EH, FK, G, GY, IM, IV, JE, KA, KW, KY, LD, LL, ML, PA, PH, PO 30-41 (Isle of Wight), SA, SY, TD, TN, TR, ZE Southern Ireland
Our lead times should only be used as a guide and are subject to change.
Offloading
Unless a hi-ab delivery has been booked at additional cost, it is the customer's responsibility to offload with suitable equipment on the day of delivery and a failed delivery may result in additional charges.
We recommend installers and/or plant hire & materials to install such as excavators, aggregates etc are not booked until you are in receipt of the goods. Tanks Direct cannot be held responsible for costs incurred due to unforeseen delays, please see our terms for more details.
HIAB
HIAB delivery will be required if you need the tank offloaded from the delivery vehicle. The driver will unload the tank from the vehicle to ground level, however this service is not to place the tank in situ, this will need to be arranged separately.
If you have any questions regarding your delivery, please contact the Sales Team on 01643 703358.
Returns Information
Please note - Certain items may not be returnable, for example those made to order or for sanitary reasons. Please check the product page for more information.
Customers may return items within 14 calendar days (as per our Terms & Conditions) - refer to section 7. **
All Items must be returned unused, refunds cannot be issued for used or previously installed items.
Please be aware that returning a tank can be complicated and expensive, so please check that you are ordering the correct item (we suggest checking the dimensions very carefully).
If you wish to return goods, please complete the form on this page to provide further information.
Once your request is approved, a valid Returns Authorisation Number (RAN) will be issued to initiate the returns process along with information on how & where to return your order along with any costs involved.
Please DO NOT return any goods without this authorisation. Goods cannot be accepted without this.
Returns are not accepted at our Minehead Office, please wait until we contact you before returning any goods.